TT-3606E startup file download






















An extended serial communication cable must not exceed 20 meters. Alarm panels can be connected to terminal block J, J and J shown in Figure The labelling of the individual terminals corresponds to the labelling in TTC. In order to prepare the cable for mounting, start by removing 12 cm. Figure 28 Preparation of cable for alarm panels Make sure the cable screen is proper folded around the cable isolation before mounting. Start by fastening the cable firmly in the cable relief bracket of the TTC before mounting the individual wires.

Then cut each wire 1. Remove 5 mm. An example is shown in Figure B or newer, refer to the label on the side of the top cover. Figure 30 Location of connector J The cable used should be shielded twisted pair 2x2x0. The total length of the cable from termination to termination should not exceed meters and the length from TTC to either end of the cable should not exceed meter. The cable screen should only be connected at the TTC. Please note, that J only accepts wires with a cross section of up to 0.

The individual units can be connected to the string using short stubs with a maximum length of 5m as shown in Figure A setup as shown in Figure 31 can be made using commercially available DeviceNet cable components. For more information on this solution please refer to Appendix D. Another kind of wiring is the one shown in Figure There are two pins for each signal in the DSUB9 connectors, thus soldering of each wire in the cable can be performed in a robust manner, provided the cable is not too thick.

Pin 6 are internally connected to pin 5 via a termination resistor of Make sure the cable shield is firmly connected to TTC using the cable relief brackets. Make sure, that the twisted pairs are actually twisted all the way to the terminal strip.

In case one of the APs are located less than 50 meters from the interconnection box, a setup as shown in Figure 33 can be used in order to save an extra power supply unit. In the following sections the interface to the E Message Terminal is described. The power input connector is a standard 15 pin SubD male connector, located on the rear panel of the TTE and the pin assignments are as indicated in Table The wire color codes are as given in Table The communication parameters are factory programmed to: COM1, speed Baud, 8 databits, no parity, 1 stopbit.

Alternatively these settings may be customer defined. The pin assignment for the two communication ports are identical. The printer port connector is located on the rear panel. TTE Keyboard does normally not require any separate grounding.

Figure 36 illustrates the dimension of the panel cut-out and position of mounting holes when mounting the TTE Message Terminal in a console. Figure 36 Mounting holes for TTE Figure 37 illustrates the position of the mounting holes for the mounting bracket. In case TTA and TTE are turned off, the Transceiver will hold the incoming messages in the internal memory for at approximately 48 hours for later Hard Coping.

The enclosed standard cable allows the printer to be located up to 1. A special low impedance cable is available for printer locations up to 20 meters from the Message Terminal.

The printer connector is located on the rear panel. The interface conforms to a standard Centronics type interface. A mounting plate is supplied with the TTA Hard Copy Printer, for horizontally oriented secured mounting see section 4.

This enables the printer to signal an advanced warning of a paper low condition, when the paper roll is almost empty. The printer continues to work, and "Printer almost out of paper" message is displayed by the message terminal.

When a "Printer almost out of paper" condition occur the audio alarm will sound and the fault indication on any connected alarm panel will be switched on - these indications continues until the paper roll is replaced. If the printer is set off-line using the "select" button or powered off using the power switch, the audio alarm and the fault indication in the alarm panels will be switched on.

The DIP switch can be accessed by removing the switch cover from the back of the printer. A distress alert can be initiated by pressing the Distress button for five seconds. The outline and dimensions for a flush mounted AP are shown in Figure Panel Mounting Bracket. Figure 44 Outline and dimensions - flush mount The drilling template is shown in Figure 45 and the 3 dimensional assembly drawing is shown in Figure Connect a grounding wire between the ships structure and AP by using the dedicated grounding point found on the rear panel of the alarm panel.

The grounding wire should have a cross section of at least 0. The pin-out is shown in Table For further information concerning wiring of the communication interface, please refer to section 4. The connector marked Power is used for: 1 Connecting power to the internal electronics of the alarm panel the isolated RS interface is powered through connector Inm-C.

As up to four APs can be connected to the same cable, they need to have their own unique address in the rang The pin-out of the Power connector is shown in Table Table 13 Pinout of "Power" connector on AP 4. Connect 24VDC between Power pin 6 negative and pin 7 positive. Do not connect the shield of the power supply cable at the alarm panel. It should be connected to ground at the source only. With full activity the maximum current will be around 36mA 24VDC.

Note 1: The unit is internally protected against reverse polarity. Subsequent APs need to get the address pins strapped according to Table Normally there is no need to access the RS service interface, but in case its necessary, the easiest method is to make a cable adapter as shown in Figure Pressing and holding the Test button will make all light indicators and the alarm button flash.

Pressing any other button while holding the Test button, will sound the buzzer enabling verification of the buttons and the audible indicator. Figure 48 System detected, unit ready.

A Distress Alert can be initiated by pressing the Distress button for five seconds. Included in the box is a Distress Relay, which makes it possible to control an external alarm panel. The function of the relay can be selected by setting two internal jumpers according to the specifications in Table 18 TTC Technical Specifications.

In case jumper W1 is set to enable the Distress Relay, it will be activated upon reception of a SafetyNet Message with distress priority. The light intensity of the green power indicator can be adjusted by a knob below it. C onsole mounting hole A Screw : holes for w mounting, 4 all B Screw : holes for console mounting, 4.

Figure 50 TTC Mounting stencil. If required, the cable relief are easily moved from the end of the TTC to the bottom feed hole for hidden cable installation. Connect each wire as indicated by the label and in accordance with the wire colour codes chosen refer to 4. Figure 51 TTC connector label Do not connect the cable screen and make sure it does not short circuit anything.

Concerning the initial start up and use of the TTE Message Terminal, please refer to the user manual, ref. The location of the LEDs is shown in Figure Spare fuse. In case the LED does not light up, then:. Check for obvious visual errors on the TTC itself wire fragments, burnt areas etc. Turn off the power supply before replacing the fuse. Note, that a spare fuse is available as indicated in Figure A flashing C OK LED indicates a software update in progress or a missing application software could be a result of an aborted software update.

Refer to ref. If so, remove the overload. Note, that some errors can only be detected when the Distress button is pressed. To perform such a test, refer to section 5. Cancel the test mode if a real distress alert needs to be sent. Please notice that the message displayed by the Message Terminal asks the operator if distress test mode should be cancelled.

Do not answer yes to this question unless you are absolutely sure that you have completed distress testing. Distress Test Mode is cancelled by pressing the Esc key. Otherwise a real Distress Alert is transmitted.

Pressing the Distress button will make the Distress LED flash and will activate an intermediate acoustic signal. If the Distress button is held for at least 5 seconds the acoustic signal will stop and the Distress LED will light constantly to indicate that a Distress Alert would have been send in case Distress Test Mode had not been activated.

When Distress Test mode is initiated, the text Test will be shown in green letters on the display line. A cyclic test sequence will: 1 Switch on the Distress text 5 seconds. All other segments on the display line will be lit constantly during the test. Pressing the Distress button will make the distress button flash and will activate an intermediate acoustic signal.

If the Distress button is held for at least 5 seconds the acoustic signal will stop and the distress button will be lit constantly to indicate that a Distress Alert would have been send in case Distress Test Mode had not been activated. A link test is initiated by clicking Options Link test. Note, that it may take up to one minute for the information about the latest Link Test to be updated.

Click Activate to start the test. After a while the window will be updated with the text: Automatic test mode: Normal communication disabled. Do not press any distress buttons unless you are in distress. The printer will print a message saying Link Test request issued, then a Link Test request successful and a Link Test started.

When receiving the results the screen will display: Link Test finished and the results will be printed out. In case the Link Test fails, then make sure, that the signal strength as indicated on the main window is OK and then try performing another Link Test.

When using the NS Power Supply, simply switch of the mains supply on the switch found on the front of the unit. Position the cursor where you want to insert the text. Select the text you want to delete. The search is always performed from the cursor and onwards. Type in the text that you want to find. The Editor searches for the exact pattern, so please watch your upper- and lowercase letters.

If the text is found the cursor is positioned immediately after the pattern. If the pattern is not found, an error message is displayed. Type in the text that you want to replace and press Enter. Type in the replacement text and press Enter. When an instance of the pattern is found, the Editor highlights the text, and you are asked whether this particular instance should be replaced or not. This will allow other programs to read your message files. Press F10 and open the Paint menu.

Up to destinations can be stored. Press F3 to access the Address Book or 2. Names of Destinations Holds the names of all your destinations. Destination data Holds the data of the highlighted Destination Name. When you move the highlight to another name, this field is updated with the data corresponding to this name. Type of destination Allows you to select different network types. Not all of the listed types may be available at a particular Land Station.

Press Spacebar on the desired type. Presentation Enables you to select whether your transmission should be done using either 5, 7 or 8 bit presentation. The 7 bit option is supported by all Land Stations. Press User Manual Spacebar on the desired Special Options You can specify that you want your message to always include the latest position and time if available when the message is sent. Capsat automatically inserts this information as text in front of your message text, if you check the Position box.

The information that Capsat inserts has the same format as what you will get if you had manually used Edit, Position Ins from the menu. If the position is not available from a built-in GPS, Capsat will ask you if you want to send the message anyway. The latest available position will then be inserted instead. If you check this box you will need to type a two digit code in the appropriate field. This two digit code will be put in front prefixed of your destination address when the message is sent.

Mark Marks up to 10 destinations by placing a mark to the left of the entry. When Select is chosen afterwards, all 10 destinations are selected. To unmark an entry choose Mark once again. Instead of using Mark, you can use the Spacebar. New Creates a new entry in the Address Book. First time you access the Address Book, it will be empty and you must select New and fill in a destination in order to use the Address Book. Revise Enables you to change the contents of a particular entry.

Erase Erases an entry from the Address Book. Options - Find Searches for a name or a part thereof. The search is sensitive to upper- and lowercase letters. Options - Save Saves the contents of the Address Book in a file on the disk.

Give the file a name of up to 8 characters. The file will be appended the extension '. Options - Load Clears the present contents of the Address Book and reads in the contents of the selected file.

Options - Print Prints the contents of the Address Book. Options - Password Enables you to protect the contents of the Address Book with a password. To clear password protection, choose this menu again and re-enter your password twice. Choose New from the menu bar and type in the name of your new destination and press Enter to move the highlight to the Destination type fields.

Move the highlight to the Number field by pressing Enter and type in the destination preceded by the country code. When addressing another Inmarsat-C mobile unit, remember to specify the Ocean Region. See table below. Press Enter to move the highlight to the OK field and press Enter once more. Type Telex Mobile Mobile X. Press F2 to access Capsat. Press Esc a number of times overlaying windows are removed.

This means that when a message is sent off, it is stored within the system for a period of time before the message is forwarded to the final destination. A message can be sent to several destinations at the same time Multi-addressing.

Maximum is Addressing the different destination types is thoroughly discussed in the chapter Capsat Address Book on page All characters represented by values from 0 to is sent transparently to the Land Station.

Values above are truncated. All characters are transmitted transparently over the satellite link. When the Land Station forwards the message this will also be done transparently if possible. Some Land Stations inserts a header in the message, which the recipient must remove before being able to use the message, if the message for instance was a spread-sheet data file. Address Field Holds the address information of your destination. Place highlight on the field and press Spacebar to access the Address Book.

The Address Book is then searched for an entry starting with these letters and if found, the data of this entry is copied to the Transmit window. Priority Selection Allows the user to give a message a special priority, to be used when handled by the Land Station. Message Selector Selects whether the text in the editor or a file on the disk should be transmitted. Send Button Sends the message when pressing Enter here. Address Book by pressing 3. Position the highlight on the desired destination and choose Select.

See also the chapter Capsat Address Book on page Position the highlight on the desired Land Station and choose Select. The message is saved in the message log on the disk along with addressing information allowing you to send the message again if necessary.

Position the highlight on the desired email destination and choose Select. Please notice that only stations that are configured to support Internet Email will be on the list please see section 5. Figure 13 Transmit Email Window 7. Only entries supported by the selected Internet Service Provider will be present.

Fill in the necessary extra information using the arrow key to move between the different fields. Move the highlight in the Transmit window to ' [X] Text in editor' and press Spacebar to remove the 'X'.

This reveals the field 'File' immediately below. Select the desired file by choosing Select. The size of the file must not exceed 10 Kb, which is the absolute maximum message length.

Move the highlight in the Transmit window to ' [X] Immediate transmission' and press Spacebar to remove the 'X'. This reveals the field 'Time' immediately below. Press Arrow Down to move highlight to the Time field and enter the time of the transmission.

Move the highlight in the Transmit window to ' [ ] Print' and press Spacebar to insert an 'X'. Distress priority transmissions are not affected. Type in your password and press Enter. Type in your password again for verification and press Enter. All transmitted messages are recorded in a message log file on the disk together with all received messages. The transmit log is automatically updated every time the status of a message is changed. The numbering will be sequential starting with ''.

Kbits Specifies how many kilobits actually sent. You will be charged per kilobit by the Land Station. Ref is the message reference number of the message as given by the Land Station. On the next page is shown the possible values of this field. Land Station.

Confirmation was not requested. ConfReq The message has been successfully received by the Land Station, but so far the delivery to the final destination hasn't been done. ConfOK The message has been delivered to final destination. You will only see ConfOk if you have requested confirmation in the Transmit window.

Otherwise you will only get 'Acknowlg'. Failed The Land Station failed to deliver a message on which confirmation had been requested or the transmission protocol failed. The failure code will be printed out. Pending The Land Station has postponed the transmission for a short time. The transmission will be done when the Land Station tells the transceiver to go ahead.

Rejected The transmission was rejected by the Land Station. NotDeliv Will only be shown, if you explicitly try to get a I. It indicates that the Land Station has not yet been able to deliver the message, but is still trying. When giving up, the status will change to 'Failed'. Unknown The message is no longer recorded in transceiver and the final status is not known.

Resubmit Send a message again. Confirm Explicitly requests confirmation status at the Land Station of a particular entry. Erase Deletes an entry from the log. You cannot delete an entry which has status 'Sending'. Print Prints out the log. Choose Resubmit R to have the Resubmit window presented. You now have the option to change the Land Station or the destination. In addition to this you may choose to have the messages printed.

The messages may also be saved in separate files on the disk. When a new message has been transferred to disk, this is indicated in the Status Field of the Capsat window with either "Mail" or "Egc-Mail". Important note. As the E system does not support a remote printer, you should always select local printer or disk.

The local printer is connected to the E Message Terminal. The Capsat program will change your routing selections if they conflict with the Inmarsat specifications: If the Message Log files box has no checkmark and none of the 3 boxes for Mail has a checkmark, then the program will put a mark in Local Prn for you. The same goes for the 4 EGC Message types.

By default all received messages are stored in the log files on the disk. The receive log is automatically updated every time the status of a message is changed. Viewing the log clears this field. Will be cleared after viewing. File Is assigned by the transceiver at the time of reception.

If you don't do a Logout before turning off you transceiver, the current number will not be saved - So always do a logout Status Indicates whether the message has been routed to local printer Prn , diskette Disk , remote printer Rmt or a combination thereof. Print Prints a message stored on disk. Logprint Prints out the log. Mail Request Send a request for mail to a Capsat Gateway. The request is sent as a datareport to a DNID.

You must set-up which DNID to use before you can send any requests. Please consult the chapter Message Routing on page The EGC messages can be divided in 3 major categories. FleetNet Information from authorised commercial Information Providers. System Supplied by Inmarsat. Table 5 gives a quick view of the different EGC services. FleetNET messages cannot be blocked.

On maritime units this also applies to SafetyNET messages. Coastal Warning Service Selection Allows you to mark 'X' the desired types of services for reception. Fixed Positions Allows you to type in 5 additional positions in order to receive EGCs addressed to geographic areas including these.

The layout and the facilities strongly resemble those of the Receive Log, which we kindly ask you to consult. The priority field in the log may show the following codes. The audio alarm is stopped by pressing the buzzer reset button on the Remote Alarm Box. A message box will be displayed on the screen and a Beep will issued at regular intervals until you remove the box by pressing Esc.

Table 6 EGC priority 5. To check your ENIDs: 1. You may edit the field by pressing Spacebar. Position Field Allows you to enter your current position. Nature of Distress Shows here the types available for Maritime Distress. The Maritime Distress Alert parameters set-up in the Distress Menu are transferred to the transceiver.

The parameters are valid in the transceiver for an hour or until a distress acknowledgement is received. Type in the message in the Text Field of the Editor.

Choose Transmit Alt, T. Press Arrow Down twice to move to ' Distress' and press Spacebar to select. If the Land Station field is empty, the highlight will be positioned there instead. Press Spacebar to get the Land Station list and select a station. Confirm the distress priority transmission by pressing Enter. It is used in EGC reception to selectively receive the messages addressed to certain areas. Also, a correct position is vital when sending Distress in case of emergency.

The transceiver has a built-in GPS unit, which ensures that your equipment knows the correct position. If your transceiver has a built-in GPS, this will be indicated in the main Capsat window as shown below.

The mode of the GPS is displayed using small boxes. See Table 7. To ease the acquisition, the approximate position and time could be entered. Upon power-up the GPS module will always enter transceiver this has a mode. The number of small boxes indicates the quality of the GPS signal. This also includes the PC or Message Terminal.

If you do not have the correct local time, please check your time-zone. Press F10, Select Options and Clock. Maritime Units Only. This warning is acknowledged using the Esc key. This indication is removed when the position has been updated.

If it isn't updated within 12 hours, the position will become invalid. Choose Position Alt, P 2. Type in the position; Longitude: degrees, minutes and hundreds of a minute and so on. Press Enter on the OK button to actually set the position. Figure 21 Setting the Position When the position is shown on the screen, the values shown will be updated by the program allowing you to monitor the position generated by a the GPS module. This makes the reporting inexpensive compare to sending a text message containing a position and time like explained in the section about Special Options on page A brief description of DNIDs is given on page This is done by Polling.

The Transceiver can control up to four connections, numbered from 0 to 3. Each of these connections can hold one reporting program, but only one of the connections can be local. This is the one that you can program from the Capsat program. The other 3 connections must be set up from a remote site via polling. Below is a example of the status of connection 0 and 1 when they are un-programmed closed. If you want to see connection 2 and 3 you can select More on the menu.

Select Change, Open from the menu. You can mark one or more from the list, but the DNIDs must be from different ocean regions. Select Program from the menu. Classic Start Menu See all features.

Classic Explorer See all features. Choose between 3 different styles: Classic Two columns Windows 7. Many usability improvements to Explorer every feature can be turned on or off :. Read the F. Ask a question in the forum Report a bug or submit a feature request Learn how to make your own skin Learn how to make your own start button. Very well made with lots of options. Makes Windows 7 worth using.

Saves me from daily frustration. Thank you so much! No more frustration, I can work just like I used to!



0コメント

  • 1000 / 1000